An intermittent trip that had closed the unit twice, traced to a soaked exterior fitting and repaired the same night.

ASN Engineering electrician performing electrical maintenance and repair work in Singapore

The tenant had lost power twice in a week, both times in the evening and both times back on after resetting — the pattern that makes an intermittent fault expensive to guess at and cheap to measure.

We attended the same night, isolated circuit by circuit and found earth leakage rising on the rear lighting way whenever it rained. The cause was an exterior fitting whose gland had perished and filled with water.

The fitting was replaced, the run was re-terminated and re-tested, and the readings were recorded. The unit opened as normal the next morning.

Planning reinstatement or renovation works?Talk to ASN Engineering today.